Event caption PQ-221: the waveform that was not 'just a blink'
← All analysis

Sector · Energy · 04 Aug 2026 · Brief

Event caption PQ-221: the waveform that was not 'just a blink'

Sag depth, duration, and ride-through class decide scrap after a dip—power-quality event caption sheet, not black-start tabletops, not UPS island cascades alone, not utility invoice autopsies.

Event: PQ-221
Source: Plant PQ monitor · Feeder West
Format: Caption sheet for one waveform. Not a harmonics textbook.


Caption block

Event ID: PQ-221
Type: voltage sag
Retained voltage: ~68% Vnom
Duration: ~1 s
Phase: A-B heavy
Time: 14:03:11 local
Upstream: utility reclose suspected

Oscilloscope-style sag waveform printout with duration marks

If duration is blank, every department invents a different story.


Who felt it

| Island / load | Effect | Expected by ride-through class? | | --- | --- | --- | | Packaging VFDs | Trip | No — class underspec'd | | UPS process island 2 | Held | Yes | | PLC cabinet (off-island) | Brown reboot | Predictable failure | | Abatement | Trip → tool abort | Not on UPS list |


Wrong narratives heard same day

  1. "Blink — ignore." (~1 s is not ignore for VFDs.)
  2. "Buy bigger UPS for everything." (No shed / class review.)
  3. "Utility fault — not our problem." (Ride-through class is yours.)

Caption → actions

  1. File PQ-221 with waveform + load effects in one packet.
  2. Reclass packaging VFDs ride-through or move controls on-island.
  3. Put abatement on the critical dependent list (see UPS island logic).
  4. Stop closing tickets as "blink" without duration.

PQ monitor HMI event list with PQ-221 highlighted

Event IDs beat hallway mythology.


Adjacent fences

Black-start scripts own grid-loss decision drills. UPS cascade essays own dip failure trees. Invoice autopsies own tariff lines. PQ-221 owns one sag as evidence. Do not fund a second generator to skip a caption sheet.


Close

A waveform without a caption is art. A caption without actions is filing. PQ-221 needs both—or the next sag reprints the scrap.